Digital Output with Shutdown Input FB6208B

Slots | |
|---|---|
| Occupied slots | 2 |
Supply | |
| Connection | backplane bus |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
| Power dissipation | 2.35 W |
| Power consumption | 2.35 W |
Internal bus | |
| Connection | backplane bus |
| Interface | manufacturer-specific bus to standard com unit |
Digital output | |
| Number of channels | 8 |
| Suitable field devices | |
| Connection | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16- |
| Current limit | 8 mA |
| Open loop voltage | 20 V |
| Line fault detection | can be switched on/off for each channel via configuration tool |
| Response time | 20 ms (depending on bus cycle time) |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
Indicators/settings | |
| LED indication | LED green: supply LED red: line fault , communication error red flashing |
| Coding | optional mechanical coding via front socket |
Directive conformity | |
| Electromagnetic compatibility | |
Conformity | |
| Electromagnetic compatibility | NE 21 |
| Degree of protection | IEC 60529 |
| Environmental test | EN 60068-2-14 |
| Shock resistance | EN 60068-2-27 |
| Vibration resistance | EN 60068-2-6 |
| Damaging gas | EN 60068-2-42 |
| Relative humidity | EN 60068-2-56 |
Ambient conditions | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 95 % non-condensing |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
| Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications | |
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14...1.5mm2) or screw terminals (0.08...1.5mm2) |
| Mass | approx. 750 g |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Data for application in connection with hazardous areas | |
| EU-Type Examination Certificate | PTB 97 ATEX 1074 U |
| Output | |
| Galvanic isolation | |
| Directive conformity | |
International approvals | |
| ATEX approval | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 |
| Mari | |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


Slots