Universal Temperature Converter KFD2-UT2-2

Описание оборудования | |
|---|---|
| Current output 0/4 mA ... 20 mA | |
General specifications | |
| Signal type | Analog input |
Functional safety related parameters | |
| Safety Integrity Level (SIL) | SIL 2 |
Supply | |
| Connection | terminals 14+, 15- or power feed module/Power Rail |
| Rated voltage | 20 ... 30 V DC |
| Ripple | within the supply tolerance |
| Power dissipation/power consumption | ? 1.53 W / 1.53 W |
Interface | |
| Programming interface | programming socket |
Input | |
| Connection side | field side |
| Connection | terminals 1, 2, 3; 4, 5, 6 |
| RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
| Thermocouples | type B, E, J, K, N, R, S, T (IEC584-1:1995) type L (DIN43710:1985) type TXK, TXKH, TXA (P8.585-2001) |
| Potentiometer | 0 ... 20 k? (2-wire connection), 0.8 ... 20 k? (3-wire connection) |
| Voltage | selectable within the range -100 ... 100 mV |
| Input resistance | ? 1 M? (-100 ... 100 mV) |
Output | |
| Connection side | control side |
| Connection | output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-) |
| Output I, II | Analog current output |
Transfer characteristics | |
| Deviation | |
| Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
Galvanic isolation | |
| Input/Other circuits | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
| Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Indicators/settings | |
| Display elements | LEDs |
| Configuration | via PACTware |
| Labeling | space for labeling at the front |
Directive conformity | |
| Electromagnetic compatibility | |
Conformity | |
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
Ambient conditions | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 130 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
По вопросу интересующей Вас продукции, пожалуйста, свяжитесь
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


Описание оборудования