Relay Module KFD2-RSH-1.2D.FL3

General specifications | |
|---|---|
| Signal type | Digital Output |
Functional safety related parameters | |
| Safety Integrity Level (SIL) | SIL 3 |
| Performance level (PL) | PL e |
Supply | |
| Connection | Power Rail or terminals 14+, 15- |
| Rated voltage | 19 ... 26.4 V DC |
| Input current | 35 mA at 24 V DC , max. 44 mA at 19 V DC , with enabled internal fault detection |
| Power consumption | < 1.7 W , includes the power consumption of the digital input , see derating curves |
Input | |
| Connection side | control side |
| Connection | terminals 7+, 8- |
| Pulse/Pause ratio | min. 150 ms / min. 150 ms with disabled internal fault detectИли отправьте нам запрос наs with enabled internal fault detection |
| Test pulse length | max. 2 ms from DO card |
| Signal level | 0-signal: -5 ... 5 V DC 1-signal: 19 ... 26.4 V DC |
| Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ? 36 mA (minimum load current DO card) |
| Inrush current | < 200 mA after 100 µs |
Output | |
| Connection side | field side |
| Connection | external voltagИли отправьте нам запрос наr/>load : terminals 6, 3 |
| Connectable voltage | 50 ... 230 V AC 60 ... 110 V DC |
| Power dissipation | < 3.3 W at 5 A , see derating curves |
| Contact loading | 253 V AC/5 A/cos ? 0.7; 30 V DC/5 A resistive load , see derating curves |
| Minimum switch current | 10 mA |
| Mechanical life | 5 x 106 switching cycles |
| Line fault detection | low voltage < 35 V AC undercurrent: 10 mA AC; overcurrent: 5.5 A AC (relay energized) breakage: 48 k?; short-circuit: 29 ? (load, relay de-energized) |
| Fuse rating | 2.5 A (scope of delivery) max. 5 AT, recommended maximum utilization of the fuse: 80 % |
Fault indication output | |
| Connection | terminals 10, 11 |
| Contact loading | 30 V DC/ 0.5 A resistive load |
| Reaction time | < 2 s |
| Mechanical life | 105 switching cycles |
Transfer characteristics | |
| Switching frequency | < 3 Hz with disabled internal fault detection < 0.5 Hz with enabled internal fault detection |
Galvanic isolation | |
| Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff |
| Input/fault indication output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 30 Veff |
| Output/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings | |
| Display elements | LEDs |
| Control elements | DIP-switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity | |
| Electromagnetic compatibility | |
| Low voltage | |
| Machinery Directive | |
Conformity | |
| Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 , EN 61326-3-1:2008 |
| Degree of prot | |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


General specifications