Frequency Converter with Trip Values KFD2-UFC-1.D
Описание оборудования | |
---|---|
24 V DC | |
General specifications | |
Signal type | Digital Input |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | terminals 23+, 24- or power feed module/Power Rail |
Rated voltage | 20 ... 30 V DC |
Rated current | approx. 100 mA |
Power dissipation/power consumption | ? 2 W / 2.2 W |
Interface | |
Programming interface | programming socket |
Input | |
Connection side | field side |
Connection | Input I: 2-wire sensor: terminals 1+, 3- three wire sensИли отправьте нам запрос на input II: terminals 13+, 14- start-up override; |
Input I | 2- or 3-wire sensor, sensor acc. to EN60947-5-6 (NAMUR) or mechanical contact |
Input II | startup override: 1 ... 1000 s, adjustable in steps of 1 s |
Output | |
Connection side | control side |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 outout III: terminasl 19+, 20- output IV: terminals 8+, 7- |
Output I, II | signal, relay |
Output III | electronic output, passive |
Output IV | analog |
Collective error message | Power Rail |
Transfer characteristics | |
Input I | |
Output I, II | |
Output IV | |
Galvanic isolation | |
Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output III/power supply and collective error | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Output III/IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Output IV/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Start-up override/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Interface/power supply and collective error | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Interface/output III | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Indicators/settings | |
Display elements | LEDs , display |
Control elements | Control panel |
Configuration | via operating buttons via PACTware |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Low voltage | |
Conformity | |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
День | Время работы |
---|---|
Понедельник | 09:00-17:00 |
Вторник | 09:00-17:00 |
Среда | 09:00-17:00 |
Четверг | 09:00-17:00 |
Пятница | 09:00-17:00 |
Суббота | Выходной |
Воскресенье | Выходной |