Solenoid Driver KFD2-SL2-Ex1.LK.1270
General specifications | |
---|---|
Signal type | Digital Output |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 30 V DC |
Power dissipation | max. 1.4 W |
Power consumption | max. 2.3 W at 70 mA output current |
Input | |
Connection side | control side |
Connection | terminals 7, 8 |
Input current | approx. 3 mA |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC |
Output | |
Connection side | field side |
Output I | |
Output II | fault signal |
Galvanic isolation | |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output II/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings | |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Low voltage | |
Conformity | |
Electromagnetic compatibility | NE 21:2007 |
Degree of protection | IEC 60529:2001 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas | |
EU-Type Examination Certificate | ZELM 99 ATEX 0015 |
Supply | |
Input | |
Collective error message | |
Certificate | TUV 02 ATEX 1820 X |
Output II | |
Galvanic isolation | |
Directive conformity | |
International approvals | |
CSA approval | |
IECEx approval | |
Accessories | |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
По вопросу интересующей Вас продукции, пожалуйста, свяжитесь с нами:
<img alt="" src=" http://www.fi</h3> |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
День | Время работы |
---|---|
Понедельник | 09:00-17:00 |
Вторник | 09:00-17:00 |
Среда | 09:00-17:00 |
Четверг | 09:00-17:00 |
Пятница | 09:00-17:00 |
Суббота | Выходной |
Воскресенье | Выходной |