Voltage Repeater HiC2095

General specifications | |
|---|---|
| Signal type | Analog input |
Functional safety related parameters | |
| Safety Integrity Level (SIL) | SIL 2 |
Supply | |
| Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage | 20.4 ... 30 V DC bus powered via Termination Board |
| Ripple | within the supply tolerance |
| Power consumption | ? 1.3 W |
Input | |
| Connection side | field side |
| Connection | SL2: 5a (common), 1a or 5b (supply -), 1b (input -) |
| Input resistance | 10 k? terminals 5a and 1b |
| Output rated operating current | SL2: 5a (common), 5b: > 10 mA at -21 V or > 20 mA at -18 V SL2: 5a (common), 1a: 3.7 ± 0.26 mA, 5.3 ± 0.34 mA or 9.0 ± 0.55 mA, dependent on switch settings (see configuration) |
| Transmission range | 0 ... -20 V |
Output | |
| Connection side | control side |
| Connection | SL1: 8a(+), 7a(-) |
| Load | min. 9 k? |
| Voltage | 0 ... -20 V |
| Output resistance | 24 ? typ., 27 ? maximum Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer. |
Transfer characteristics | |
| Deviation | DC transfer error (with 10 k? load) < 10mV |
| Bandwidth | -0.1 dB at 10 kHz; -1 dB at 20 kHz |
| Time delay relative to input | 7.0 ± 0.3 µs |
| Ripple | in 200 kHz bandwidth < 20 mVrms in 20 kHz bandwidth < 3 mVrms |
Galvanic isolation | |
| Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings | |
| Display elements | LED |
| Control elements | DIP-switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
Directive conformity | |
| Electromagnetic compatibility | |
Conformity | |
| Electromagnetic compatibility | NE 21:2006 For further information see system description. |
| Degree of protection | IEC 60529 |
| Protection against electrical shock | UL 61010-1 |
Ambient conditions | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
| Degree of protection | IP20 |
| Mass | approx. 100 g |
| Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
| Mounting | on Termination Board |
| Coding | pin 2 trimmed For further information see system description. |
Data for application in connection with hazardous areas | |
| EU-Type Examination Certificate | BASEEFA 11 ATEX 0021X |
| Output | |
| Certificate | BASEEFA 11 ATEX 0022X |
| Galvanic isolation | |
| Directive conformity | |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


General specifications