SMART Universal Barrier HiC2441

Описание
Информация для заказа
General specifications | |
|---|---|
| Signal type | Universal |
Functional safety related parameters | |
| Safety Integrity Level (SIL) | SIL 2 |
Supply | |
| Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage | 19 ... 30 V DC via Termination Board |
| Ripple | ? 10 % |
| Rated current | ? 30 mA |
| Power consumption | ? 700 mW |
Analog input | |
| Suitable field devices | 2-wire SMART transmitters, current sources |
| Signal | 0/4 ... 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected |
| Field circuit | SL2: 5a(+), 5b(-) (2-wire SMART transmitter) SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source) |
| Voltage drop | approx. 4 V (current source) |
| Control circuit | SL1: 8a(+), 7a(-) |
| Supply voltage | min. 16 V at 20 mA (2-wire SMART transmitter) |
| Voltage | 15 ... 30 V |
| Signal | 0/4 ... 20 mA , sink mode , working voltage 15 ... 30 V |
| Ripple | 20 mV rms |
Analog output | |
| Suitable field devices | I/P converters (positioner), on-site-displays |
| Signal | 0/4 ... 20 mA |
| Field circuit | SL2: 5a(+), 5b(-) |
| Load | 0 ... 650 ? |
| Voltage | ? 13 V at 20 mA |
| Ripple | 20 mV rms |
| Control circuit | SL1: 8a(+), 7a(-) |
| Voltage | 12 ... 30 V |
| Signal | 0/4 ... 20 mA |
| Line fault detection | > 100 k? at max. 30 V, with field wiring open |
Digital input | |
| Field circuit | SL2: 5a(+), 1a(-) (NAMUR sensor) SL2: 5a(+), 5b(-) (dry contact) |
| Suitable field devices | NAMUR sensors according to IEC/EN 60947-5-6, dry contacts |
| Signal | 0.1 ... 9 mA , sink mode |
| Open loop voltage | approx. 10 V DC , 1 k? series resistance |
| Signal | 0.1 ... 9 mA |
| Control circuit | SL1: 8a(+), 7a(-) |
| Voltage | 13 ... 30 V |
Digital output | |
| Field circuit | SL2: 5a(+), 5b(-) |
| Suitable field devices | solenoid valves, acoustic or visual alarms |
| Drive capability | 12 V / 40 mA at 300 ? load |
| Open loop voltage | approx. 22 V |
| Current limit | 45 mA |
| Internal resistor | min. 240 ? |
| Control circuit | SL1: 8a(+), 7a(-) |
| Voltage | 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC |
| Current | 1-signal: 0 ... 45 mA, depending on the output load 0-signal: < 0.1 mA, independent of the output load |
| Power dissipation | 1.1 W at 24 V, 300 ? load (digital output) |
Transfer characteristics | |
| Deviation | ? ±60 µA incl. linearity, hysteresis and supply fluctuations at 0 ... 45 mA (digital output) |
| Switching frequency | ? 500 Hz with 50 % duty cycle (digital input, NAMUR sensor) ? 5 Hz (digital input, dry contact) ? 20 Hz (digital output) |
| Frequency range | |
- Цена: Цену уточняйте
Информация для покупателя
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


General specifications