AS-Interface analog module VBA-4E-G11-I-F

Описание оборудования | |
|---|---|
| G11 analog module 4 analog current inputs | |
General specifications | |
| Slave type | Standard slave |
| AS-Interface specification | V3.0 |
| Required master specification | ? V2.1 |
| UL File Number | E223772 |
Functional safety related parameters | |
| MTTFd | 180 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
Indicators/operating means | |
| LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
| LED ANALOG | status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range |
| LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
| LED INT/EXT | status display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage |
Electrical specifications | |
| Auxiliary voltage (output) | 20 ... 30 V DC PELV |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current | ? 60 mA (without sensors) / max. 200 mA |
| Protection class | III |
| Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input | |
| Number/Type | 4 Inputs 0/4 ... 20 mA |
| Supply | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) |
| Current loading capacity | ? 140 mA from AS-Interface; overload and short-circuit resistant ? 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected |
| Input resistance | max. 70 ? |
| Accuracy | 0.1 % of full-scale value |
| Resolution | 16 Bit |
| Temperature influence | 0.0025 %/K of input signal range |
Directive conformity | |
| Electromagnetic compatibility | |
Standard conformity | |
| Degree of protection | EN60529:2000 |
| Fieldbus standard | EN62026-2:2013 |
| Input | EN 61131-2:2007 |
| Emitted interference | EN 61000-6-4:2007 |
| AS-Interface | EN62026-2:2013 |
| Noise immunity | EN61000-6-2:2005, EN61326-1:2006, EN62026-2:2013 |
Programming instructions | |
| Profile | S-7.3.E |
| IO code | 7 |
| ID code | 3 |
| ID1 code | F |
| ID2 code | E |
| Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i) | function |
Ambient conditions | |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity | 85 % , noncondensing |
| Climatic conditions | For indoor use only |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


Описание оборудования