AS-Interface analog module VBA-4E-G11-I-F
Описание оборудования | |
---|---|
G11 analog module 4 analog current inputs | |
General specifications | |
Slave type | Standard slave |
AS-Interface specification | V3.0 |
Required master specification | ? V2.1 |
UL File Number | E223772 |
Functional safety related parameters | |
MTTFd | 180 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Indicators/operating means | |
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
LED ANALOG | status of input signal; LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range |
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
LED INT/EXT | status display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage |
Electrical specifications | |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ? 60 mA (without sensors) / max. 200 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input | |
Number/Type | 4 Inputs 0/4 ... 20 mA |
Supply | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) |
Current loading capacity | ? 140 mA from AS-Interface; overload and short-circuit resistant ? 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected |
Input resistance | max. 70 ? |
Accuracy | 0.1 % of full-scale value |
Resolution | 16 Bit |
Temperature influence | 0.0025 %/K of input signal range |
Directive conformity | |
Electromagnetic compatibility | |
Standard conformity | |
Degree of protection | EN60529:2000 |
Fieldbus standard | EN62026-2:2013 |
Input | EN 61131-2:2007 |
Emitted interference | EN 61000-6-4:2007 |
AS-Interface | EN62026-2:2013 |
Noise immunity | EN61000-6-2:2005, EN61326-1:2006, EN62026-2:2013 |
Programming instructions | |
Profile | S-7.3.E |
IO code | 7 |
ID code | 3 |
ID1 code | F |
ID2 code | E |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. |
Parameter bits (programmable via AS-i) | function |
Ambient conditions | |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком