Inductive sensor NJ10-30GK-N-15M
General specifications | |
---|---|
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 10 mm |
Installation | flush |
Assured operating distance | 0 ... 8.1 mm |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.85 |
Output type | 2-wire |
Nominal ratings | |
Nominal voltage | 8 V |
Switching frequency | 0 ... 300 Hz |
Current consumption | |
Compliance with standards and directives | |
Standard conformity | |
Approvals and certificates | |
EAC conformity | TRCU 012/2011 |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated ?36 V |
Ambient conditions | |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications | |
Connection type | cable PVC , 15 m |
Core cross-section | 0.75 mm2 |
Housing material | PBT |
Sensing face | PBT |
Degree of protection | IP66 / IP68 |
Cable | |
Equipment protection level Gb | |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 2G Ex ia IIC T6…T1 Gb The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
Appropriate type | NJ 10-30GK...-N... |
Effective internal inductivity | max. 140 nF ; a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. |
Equipment protection level Da | |
CE marking | [*PD-Z02585A*] |
ATEX marking | II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
Appropriate type | NJ 10-30GK...-N... |
Effective internal inductivity | max. 140 nF ; a cable length of 10 m is considered. |
Effective internal inductance | max. 100 µH ; a cable length of 10 m is considered. |
Maximum permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. |
General information | |
Use in the hazardous area | see instruction manuals |
По вопросу интересующей Вас продукции, пожалуйста, свяжитесь с нами:
<h3 style="t- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
День | Время работы |
---|---|
Понедельник | 09:00-17:00 |
Вторник | 09:00-17:00 |
Среда | 09:00-17:00 |
Четверг | 09:00-17:00 |
Пятница | 09:00-17:00 |
Суббота | Выходной |
Воскресенье | Выходной |