General specifications | |
---|---|
Switching function | Normally open (NO) |
Output type | PNP |
Rated operating distance | 4 mm |
Installation | flush |
Output polarity | DC |
Assured operating distance | 0 ... 3.24 mm |
Reduction factor rAl | 0.45 |
Reduction factor rCu | 0.35 |
Reduction factor r304 | 0.7 |
Nominal ratings | |
Operating voltage | 10 ... 30 V DC |
Switching frequency | 0 ... 1000 Hz |
Hysteresis | typ. 5 % |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | pulsing |
Voltage drop | ? 3 V |
Operating current | 0 ... 150 mA |
Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C |
No-load supply current | ? 15 mA |
Switching state indicator | LED, yellow |
Functional safety related parameters | |
MTTFd | 1820 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Approvals and certificates | |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated ?36 V |
Ambient conditions | |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications | |
Connection type | cable PVC , 2 m |
Cable version | PBT |
Core cross-section | 0.14 mm2 |
Housing material | brass, nickel-plated |
Sensing face | PBT |
Housing diameter | 12 mm |
Degree of protection | IP67 |
Cable | |
Equipment protection level Gc (nA) | |
Certificate of Compliance | PF 15CERT3754 X |
Special conditions | |
Equipment protection level Dc (tc) | |
Instruction | Manual electrical apparatus for hazardous areas |
Device category 3D | for use in hazardous areas with combustible dust |
Certificate of Compliance | PF 15CERT3774 X |
CE marking | [*PD-Z02586A*] |
ATEX marking | II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label. |
Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure "tc" Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
General | The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. |
Installation, commissioning | Laws and/or regulations and standaИли отправьте нам запрос наtended usage goal must be observed. If the Ex-relevant identification is printed exclusively on the adhesive lab |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
День | Время работы |
---|---|
Понедельник | 09:00-17:00 |
Вторник | 09:00-17:00 |
Среда | 09:00-17:00 |
Четверг | 09:00-17:00 |
Пятница | 09:00-17:00 |
Суббота | Выходной |
Воскресенье | Выходной |