Inductive sensor NJ1,5-8GM-N

General specifications | |
|---|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 1.5 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.215 mm |
| Actual operating distance | 1.35 ... 1.65 mm typ. |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.3 |
| Reduction factor r304 | 0.85 |
| Output type | 2-wire |
Nominal ratings | |
| Nominal voltage | 8.2 V (Ri approx. 1 k?) |
| Switching frequency | 0 ... 5000 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
| Current consumption | |
Functional safety related parameters | |
| Safety Integrity Level (SIL) | SIL 2 |
Compliance with standards and directives | |
| Standard conformity | |
Approvals and certificates | |
| EAC conformity | TRCU 012/2011 |
| FM approval | |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated ?36 V |
Ambient conditions | |
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications | |
| Connection type | cable PVC , 2 m |
| Core cross-section | 0.14 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Degree of protection | IP66 / IP67 |
| Cable | |
Data for application in connection with hazardous areas | |
| Equipment protection level | Ga , Gb , Da , Mb |
Equipment protection level Ga | |
| Type of protection | intrinsic safety |
| CE marking | [*PD-Z02585A*] |
| Certificates | |
| Effective internal inductivity | max. 30 nF A cable length of 10 m is considered. |
| Effective internal inductance | max. 50 µH A cable length of 10 m is considered. |
| Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. |
Equipment protection level Gb | |
| Type of protection | intrinsic safety |
| CE marking | [*PD-Z02585A*] |
| Certificates | |
| Effective internal inductivity | max. 30 nF A cable length of 10 m is considered. |
| Effective internal inductance | max. 50 µH A cable length of 10 m is considered. |
| Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW , T6 : 68 °C (154.4 °F) T5 : 83 °C (181.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C ( |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


General specifications