Inductive sensor NJ40+U1+N

General specifications | |
|---|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 40 mm |
| Installation | non-flush |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.3 |
| Reduction factor r304 | 0.85 |
| Output type | 2-wire |
Nominal ratings | |
| Nominal voltage | 8.2 V (Ri approx. 1 k?) |
| Switching frequency | 0 ... 80 Hz |
| Current consumption | |
Functional safety related parameters | |
| MTTFd | 2588 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives | |
| Standard conformity | |
Approvals and certificates | |
| EAC conformity | TRCU 012/2011 |
| FM approval | |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated ?36 V |
Ambient conditions | |
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications | |
| Connection type | screw terminals |
| Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
| Core cross-section | up to 2.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
| Note | Tightening torque: 1.8 Nm (housing) |
Equipment protection level Ga | |
| CE marking | [*PD-Z02585A*] |
| ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
| Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
| Appropriate type | NJ 40+...+N... |
| Effective internal inductivity | max. 180 nF ; a cable length of 10 m is considered. |
| Effective internal inductance | max. 130 µH ; a cable length of 10 m is considered. |
| Ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1. |
Equipment protection level Gb | |
| CE marking | [*PD-Z02585A*] |
| ATEX marking | II 1G Ex ia IIC T6…T1 Ga The Ex-related marking can also be printed on the enclosed label. |
| Standards | EN60079-0:2012+A11:2013, EN60079-11:2012 Ignition protection "Intrinsic safety" Use is restricted to the following stated conditions |
| Appropriate type | NJ 40+...+N... |
| Effective internal inductivity | max. 180 nF ; a cable length of 10 m is considered. |
- Цена: Цену уточняйте
ООО «ФилФар Технолоджи»
220036, г. Минск, ул. Западная, д.13, к.519
Дата регистрации в Торговом реестре/Реестре бытовых услуг: 18.03.2015
Номер в Торговом реестре/Реестре бытовых услуг: 220993, Республика Беларусь
УНП: 192123248
Регистрационный орган: Минский горисполком
Дата регистрации компании: 18.09.2013
Ссылка на свидетельство/лицензию
Режим работы:
| День | Время работы |
|---|---|
| Понедельник | 09:00-17:00 |
| Вторник | 09:00-17:00 |
| Среда | 09:00-17:00 |
| Четверг | 09:00-17:00 |
| Пятница | 09:00-17:00 |
| Суббота | Выходной |
| Воскресенье | Выходной |


General specifications
II 1G Ex ia IIC T6…T1 Ga