Ordering details | |
---|---|
Product type description | EX-BNS 250-11Z-3G/D |
Article number | 101179979 |
EAN Code | 4030661332598 |
eCl@ss | 27-27-24-02 |
Approval | |
Approval | ATEX |
Classification | |
Standards | EN ISO 13849-1 |
B10d Normally-closed contact/Normally open contact (NC/NO) | 25.000.000 |
- notice | at max. 20% contact load |
Mission time | 20 Years |
notice | ![]() |
Global Properties | |
Permanent light | EX-BNS 250 |
Standards | EN 60079-0, EN 60079-15, EN 60079-31, IEC 60947-5-3, EN 13463-1, EN 13463-5, BG-GS-ET-14 |
Compliance with the Directives (Y/N) ![]() | Yes |
Materials | |
- Material of the housings | Plastic, glass-fibre reinforced thermoplastic |
- Material of the cable mantle | PVC |
Housing construction form | Block |
Weight | 43 |
Coding available (Y/N) | Yes |
Monitoring function of downstream devices (Y/N) | No |
Prerequisite evaluation unit | Yes |
Recommended safety-monitoring module | |
Recommended actuator | EX-BPS 250-3G/D |
Mechanical data | |
Design of electrical connection | Cable |
Cable length | 1 |
Conductors | 4 x 0,25 |
AWG-Number | 23 |
mechanical installation conditions | not flush |
Active area | front side |
Ensured switch distance ON Sao | 4 mm |
Ensured switch distance OFF Sar | 14 mm |
Type of actuation | Magnet |
Direction of motion | head-on with regard to the active surface |
restistance to shock | 30 g / 11 ms |
Resistance to vibration | 10 … 55 HZ, Amplitude 1 mm |
Impact energy | max. 1 Nm |
Ambient conditions | |
Ambient temperature | |
- Min. environmental temperature | −25 °C |
- Min. environmental temperature | −25 |
- Max. environmental temperature | +70 |
Storage and transport temperature | |
- Min. Storage and transport temperature | −25 |
- Min. Storage and transport temperature | −25 °C |
- Max. Storage and transport temperature | +70 °C |
- Max. Storage and transport temperature | +70 |
Protection class | IP67 |
Electrical data | |
Integrated Safety monitoring module available (Y/N) | No |
Cross circuit/short circuit recognition possible (Y/N) | Yes |
Voltage type | VDC |
Switch frequency | max. 5 HZ |
Switching voltage | 24 VDC max. |
Switching current | 100 mA max. |
Switching capacity | 1 W max. |
Outputs | |
Design of control output | Other, Reed contakts |
Number of shutters | 1 |
Number of openers | 1 |
Electrical data - Safety outputs | |
Number of secure semi-conductor outputs | 0 |
Number of secure outputs with contact | 0 |
Electrical data - Diagnostic output | |
Number of semi-conductor outputs with signaling function | 0 |
Number of outputs with signaling function that already have a contact | 0 |
LED switching conditions display | |
LED switching conditions display (Y/N) | No |
ATEX | |
EX-marking | EX II 3D Ex tc IIIC T80°C Dc X EX II 3G Ex nC IIC T6 Gc X |
Explosion protection categories for gases | 3G |
Explosion protection Zones for gases | 2 |
Explosion protected category for dusts | 3D |
Explosion protection Zones for dusts | 22 |
Dimensions | |
Dimensions of the sensor | |
- Width of sensor | 33 |
- Height of sensor | 25 |
- Length of sensor | 13 |
notice | |
Contact symbols shown for the closed condition of the guard device. | |
The contact configuration for versions with or without LED is identical. | |
Included in delivery | |
Actuators must be ordered separately. | |
Keywords | |
Keywords | Ex, EEx, ATEX, Ex BNS250, Ex BNS 250, BNS250 Ex, BNS250ex, BNS 250ex, ATEX BNS 250 |
Diagram | |
![]() Note Diagram ![]() ![]() ![]() ![]() ![]() |
По вопросу интересующей Вас продукции, пожалуйста, свяжитесь с нами:
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |
Или отправьте нам запрос на e-mail: zapros@filfar.by